Determination of the relationship among air velocity, cooling efficiency and temperature decrease at a cellulose based evaporative cooling pad

dc.authoridKARACA, CENGIZ/0000-0001-5161-1512
dc.contributor.authorDagtekin, Metin
dc.contributor.authorKaraca, Cengiz
dc.contributor.authorSangun, Levent
dc.contributor.authorYildiz, Yilmaz
dc.date.accessioned2024-09-18T20:19:55Z
dc.date.available2024-09-18T20:19:55Z
dc.date.issued2010
dc.departmentHatay Mustafa Kemal Üniversitesien_US
dc.description.abstractThe aim of this study is to determine the relationship between air velocity, cooling efficiency and decrease of the temperature of the air passing the pad, at a cellulose based evaporative cooling pad and to gain handy information for the persons working on this subject. In the study, cellulose based evaporative cooling pad (CELdek R 7060-15) was handled as material. As for the velocity of air passing through the pad 0.5, 1.0 and 2.0 ms(-1) values were selected. Based on the measurement results, cooling efficiency and provided decrease of the temperature of the air passing the pad, were calculated. As a result of the research, cooling activities calculated between 3 different air velocities were found significant in the statistical sense ( p < 0.01) for the measurement periods except II. measurement periods. As for the temperature decrease, the difference between other measurement periods except II. and III. measurement periods, were also found significant. The highest cooling activity and temperature decreases were reached at 0.5 and 1.0 ms(-1) air velocities. It can be said that according to statistical data, optimal air velocity for the Mediterranean climatic conditions should be between 0.5 and 1.0 ms(-1), among the selected air velocities.en_US
dc.identifier.endpage3482en_US
dc.identifier.issn1991-637X
dc.identifier.issue24en_US
dc.identifier.scopus2-s2.0-79251525870en_US
dc.identifier.scopusqualityN/Aen_US
dc.identifier.startpage3477en_US
dc.identifier.urihttps://hdl.handle.net/20.500.12483/9953
dc.identifier.volume5en_US
dc.identifier.wosWOS:000286331800018en_US
dc.identifier.wosqualityQ3en_US
dc.indekslendigikaynakWeb of Scienceen_US
dc.indekslendigikaynakScopusen_US
dc.language.isoenen_US
dc.publisherAcademic Journalsen_US
dc.relation.ispartofAfrican Journal of Agricultural Researchen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectEvaporative cooling paden_US
dc.subjectcooling efficiencyen_US
dc.titleDetermination of the relationship among air velocity, cooling efficiency and temperature decrease at a cellulose based evaporative cooling paden_US
dc.typeArticleen_US

Dosyalar

Orijinal paket
Listeleniyor 1 - 1 / 1
[ N/A ]
İsim:
Tam Metin / Full Text
Boyut:
183.66 KB
Biçim:
Adobe Portable Document Format