Bir ameliyathanenin iklimlendirilmesi süresince hava akımının modellenmesi

dc.authorid0000-0002-1255-9990en_US
dc.contributor.authorPolat, Yasin
dc.contributor.authorYağlı, Hüseyin
dc.contributor.authorYıldız, Koç
dc.date.accessioned2021-04-06T06:59:43Z
dc.date.available2021-04-06T06:59:43Z
dc.date.issued2019en_US
dc.departmentFen Bilimleri Enstitüsüen_US
dc.description.abstractGünümüz ameliyathanelerinin iklimlendirilmesinde kullanılan klima sistemleriyle; sıcaklık ve nem kontrolünün yapılmasının istenmesinin yanı sıra havada taşınabilen mikroorganizma ve toz miktarının, atık anestezi gazı ve kötü koku oranının önemli ölçüde azaltması da istenmektedir. Ayrıca kullanılan klima sistemleri ile standartlarda belirtilen koruma alanının oluşturabilmesi hedeflenmektedir. Bu sayede ameliyat esnasında kesi yapılan bölgeden hastaya enfeksiyon bulaşma riski de en aza indirgenebilmelidir. Bu nedenle mevcut çalışmada, Türkiye’de mevcut durumda bulunan bir devlet hastanesinin ameliyathanesinin iklimlendirilmesi sonucunda oluşabilecek sıcaklık dağılımları incelenmiştir. Çalışma kapsamında ameliyathanenin incelenmesinde iki farklı model (Model 1 ve Model 2) tasarlanmış ve tasarlanan bu modeller ANSYS Fluent programı ile simüle edilerek sayısal olarak analiz edilmiştir. Model 1 tavandan üfleme, kenarlardan emme menfezleri ile hava emen bir sistem olarak tasarlanırken Model 2 aseptizör cihazı ile iklimlendirme yapacak şekilde tasarlanmıştır. Tasarlanan her bir model için x düzlemi boyunca beş ve z düzlemi boyunca üç farklı kesitte inceleme yapılmıştır. Çalışma sonucunda, Model 1’de ameliyat lambalarının cerrahi alan üzerinde konumlandırılması sonucu ölü kış bölgelerinin oluştuğu görülmüştür. Ayrıca bu modelde incelenen kesitlerde salondaki sıcaklık değerlerinin personeli ve hastayı rahatsız edici değerler olmadığı görülmüştür. Model 2’de yüksek hava akış hızı nedeniyle ameliyathane personelinin konforsuzluk yaşadığı, cerrahi alan üzerinde laminer akışın sağlanamaması nedeniyle de cerrahi alan enfeksiyonu gelişiminin mümkün olabileceği görülmüştür. Çalışmanın sonuçları incelendiğinde, standartlara ve literatürdeki çalışmaların sonuçlarına paralel olarak ameliyathanelerde en uygun havalandırma tekniğinin bu çalışmada Model 1 olarak tanımlanan tavandan üfleme ve kenarlardan emme menfezleri ile hava emen iklimlendirme sistemi olduğu görülmüştür.en_US
dc.description.abstractWith the air conditioning systems used in the air conditioning of today's operating rooms; it is desirable that the amount of microorganism and powder that can be carried in the air to be significantly reduced as well as the temperature, humidity, waste anaesthesia gas, the odour ratio control. In addition, it is aimed to be able to form the protection area specified in the standards with the air-conditioning systems used. In this way, the risk of infection to the patient from the incision site during the operation should be minimized. Therefore, in the present study, the temperature distribution in an operating room of a state hospital in Turkey were examined. In the study, two different models (Model 1 and Model 2) were designed and the designed models were numerically analysed and simulated by using ANSYS Fluent software. Model 1 is designed as a system that blows air from the ceiling, sucking air from the sides with suction grilles, while the Model 2 is designed to air-conditioning with the aseptizer. For each designed model, five different sections along the x-plane and three along the z-plane were examined. In Model-1, it was observed that the dead winter regions were formed as a result of the positioning of the surgical lamps on the surgical area. In addition, it was observed that the temperature values in the room were not disturbing for the personnel and the patient. Because of the high air flow rate in the Model 2, it was seen that the operating room is uncomfortable the personnel due to high air flow rate and also surgical area infection development is possible due to the lack of laminar flow on the surgical area. When the results of the study are examined, it is seen that the most suitable air-conditioning system for the operating rooms in accordance with the standards and the results of the studies in the literature is air-blowing from the ceiling and air-sucking from the sides with suction grilles system, which is defined as Model 1 in the present study.en_US
dc.identifier.citationPOLAT Y,YAĞLI H,KOÇ Y (2019). Bir Ameliyathanenin İklimlendirilmesi Süresince Hava Akımının Modellenmesi. Avrupa Bilim ve Teknoloji Dergisi, 0(15), 420 - 432. Doi: 10.31590/ejosat.531362en_US
dc.identifier.doi10.31590/ejosat.531362en_US
dc.identifier.endpage432en_US
dc.identifier.issn2148-2683
dc.identifier.issue15en_US
dc.identifier.startpage420en_US
dc.identifier.trdizinid358715en_US
dc.identifier.urihttps://dx.doi.org/10.31590/ejosat.531362
dc.identifier.urihttps://hdl.handle.net/20.500.12483/3204
dc.identifier.volume0en_US
dc.indekslendigikaynakTR-Dizinen_US
dc.language.isotren_US
dc.publisherOsman Sağdıçen_US
dc.relation.ispartofAvrupa Bilim ve Teknoloji Dergisien_US
dc.relation.publicationcategoryMakale - Ulusal Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.subjectAmeliyathaneen_US
dc.subjectİklimlendirmeen_US
dc.subjectAseptizören_US
dc.subjectModellemeen_US
dc.subjectFluenten_US
dc.subjectOperating Roomen_US
dc.subjectAir Conditioningen_US
dc.subjectAseptizeren_US
dc.subjectModellingen_US
dc.titleBir ameliyathanenin iklimlendirilmesi süresince hava akımının modellenmesien_US
dc.title.alternativeModelling of air flow during air conditioning in an operating roomen_US
dc.typeArticleen_US

Dosyalar

Orijinal paket
Listeleniyor 1 - 1 / 1
Yükleniyor...
Küçük Resim
İsim:
Polat-Yasin-2019.pdf
Boyut:
1.78 MB
Biçim:
Adobe Portable Document Format
Açıklama:
Tam metin / Full text
Lisans paketi
Listeleniyor 1 - 1 / 1
[ N/A ]
İsim:
license.txt
Boyut:
1.44 KB
Biçim:
Item-specific license agreed upon to submission
Açıklama: